User Manual
SUN-10K-G03-LV
SUN-15K-G02-LV
SUN-12K-G02-LV
Grid-connected PV Inverter
1. Introduction
1.1 Appearance Introduction
1.2 Parts list
2. Safety warnings and instructions
2.1 Safety signs
2.2 Safety instructions
2.3 Notes for using
3. Operation Interface
3.1 Interface View
3.2 Status Indicator
3.3 Buttons
3.4 LCD Display
4. Product installation
4.1 Select installation location
4.2 Inverter Installation
5. Electrical Connection
5.1 DC input terminal connection
5.2 AC input terminal connection
5.3 The connection of the ground line
- 01 -
- 01 -
- 02 -
- 03 -
- 03 -
- 03 -
- 04 -
- 05 -
- 05 -
- 05 -
- 06 -
- 06-
- 07 -
- 07 -
- 09 -
- 11 -
- 11 -
- 13 -
- 16 -
…………………………………………………………
…………………………………………
………………………………………
…………………………………………………………
…………………………………………………………
…………………………………………………
……………………………………………………
……………………………………………………
……………………………………………………
……………………………………………………
………………………………………………………
……………………………………………………
…………………………………………………………
……………………………………………
…………………………………………………
………………………………………
………………………………………
…………………………………
…………………………………………………
- 17 -
…………………………………
5.4 Max. over current protection device
5.5 Inverter monitoring connection - 17 -
…………………………………
5.7 Configuration of Datalogger
6. Startup and Shutdown
6.1 Start up the inverter
6.2 Inverter Shutdown
- 18 -
- 18 -
- 18 -
- 19 -
- 19 -
…………………………………………
5.6 Installation of datalogger …………………………………………
…………………………………………………
…………………………………………………
…………………………………………………
- 20 -
…………………………………
- 20 -
………………………………
- 21 -
…………………………………
7. Zero export function via SUN limiter
7.1 SUN Limiter function wiring diagram
7.2 Connect the SUN limiter to inverter
- 23 -
…………………………………………
7.3 Use of zero export function
8. General Operation
8.1 The initial interface
8.2 Submenus in the Main Menu
8.3 System param setting
8.4 Running param set
- 31 -
- 31-
- 33 -
- 35 -
- 35 -
……………………………………………………
………………………………………………
…………………………………………………
- 24 -
…………………………………
- 29 -
- 29 -
………………………………
……………………………………………………
- 50 -
- 50 -
- 50 -
- 55 -
………………………………………………
…………………………………
…………………………………………………………
………………………………………………………
9. Repair and Maintenance
10. Error information and processing
10.1 Error code
11. Specification
8.6 Comm. param set
8.5 Protect Param - 47 -
- 49 -
……………………………………………………
……………………………………………………
………………………………………
7.5 Notes while using zero export function
7.4 Zero-export function (Option)
7.6 How to browse the load power of your PV grid-tieplant on monitoring platform
- 01 -
On-grid inverter can convert solar panel DC power into AC power which can directly input to
the grid. Its appearance is shown below. These models contain SUN-10K-G03-LV,
SUN-12K-G02-LV, SUN-15K-G02-LV.

Pic 1.1 Front view 
1.1 Appearance Introduc�on
Photovoltaic Grid-connected System
1. Introduc�on

Inverter MeteringPV array Power grid
Family load
ACDC Alar mNor m al
About This Manual


How to Use This Manual

Contents may be periodically
updated or revised due to product development. The informa�on in this manual is subject to
change without no�ce. The latest manual can be acquired via service@deye.com.cn
- 03 -
2. Safety warnings and instruc�ons
2.1 Safety signs
2.2 Safety instruc�ons
Improper use may result in poten�al electric shock hazards or burns. This manual contains
important instruc�ons that should be followed during installa�on and maintenance. Please
read these instruc�ons carefully before use and keep them for future reference.
Safety symbols used in this manual, which highlight poten�al safety risks and important safety
informa�on, are listed as follows:
Shock Hazard:
Cau�on, risk of electric shock symbol indicates important safety instruc�ons,
which if not correctly followed, could result in electric shock.
High Temperature Hazard:
Cau�on, hot surface symbol indicates safety instruc�ons, which if not correctly
followed, could result in burns.
Safety Hint:
Note symbol indicates important safety instruc�ons, which if not correctly
followed, could result in some damage or the destruc�on of the inverter.
Warning:
Warning symbol indicates important safety instruc�ons, which if not correctly
followed, could result in serious injury or death.
Shock Hazard:
Prohibit disassembling inverter case, there exis�ng shock hazard, which may
cause serious injury or death, please ask qualified person to repair.
Warning:
Electrical installa�on of the inverter must conform to the safety opera�on rules
of the country or local area.
Warning:
Inverter adopts non-isolated topology structure, hence must insure DC input and
AC output are electrical isolated before opera�ng the inverter.
Strictly prohibit grounding the posi�ve and nega�ve poles of the PV string.
Otherwise it will damage the inverter.
- 04 -
2.3 Notes for using

It can ensure the personal safety of the user. But as a electric device, it may cause shock or





 


obtaining the permission of the local power supply department, the professionals can
connect the inverter to the grid.

6. Please install where children can not touch.


disconnect the DC side.


Shock Hazard:


Shock Hazard:
While disconnect the input and output of the inverter for maintenance, please

High Temperature Hazard:
 
Please do not touch the inverter case.
- 05 -
3.2 Status Indicator
3. Opera�on Interface
Pic 3.1 Front panel display
3.1 Interface View
ACDC AlarmNormal
There are four LED status indicator lights in the front panel of the inverter. Please see table 3.1
for details.
Explanaon
Inverter detects DC input
Low DC input voltage
Grid Connected
Grid Unavailable
Under normal opera�ng
Stop opera�ng
Detected faults or report faults
Under normal opera�ng
Indicator status
DC
AC
NORMAL
ALARM
on
off
on
off
on
off
on
off
Table 3.1 Status indicator lights
- 06 -
3.3 Bu�ons
3.4 LCD Display









Esc Up Down Enter
- 07 -
4.1 Select installa�on loca�on
4. Product installa�on
To select a loca�on for the inverter, the following criteria should be considered:
WARNING: Risk of fire
● Do not install the inverter in areas containing highly flammable materials or gases.
● Do not install the inverter in poten�ally explosive atmospheres.
● Do not install in small closed spaces where air can not circulate freely. To avoid overhea�ng,
always make sure the flow of air around the inverter is not blocked.
● Exposure to direct sunlight will increase the opera�onal temperature of the inverter and
may cause output power limi�ng. It is recommended that inverter installed to avoid direct
sunlight or raining.
● To avoid overhea�ng ambient air temperature must be considered when choosing the
inverter installa�on loca�on. It is recommended that using a sun shade minimizing direct
sunlight when the ambient air temperature around the unit exceeds 100°F/40.
Pic 4.1 Recommended installa�on place
- 08 -
● Install on a wall or strong structure capable of bearing the weight.
● Install ver�cally with a maximum incline of +/-15°. If the mounted inverter is �lted to an
angle greater than the maximum noted, heat dissipa�on can be inhibited, and may result in
less than expected output power.
● If install more than one inverter, must leave at least 500mm gap between each inverter. And
each inverter must be at least 500mm above and below.And must install the inverter at the
place where children cannot touch. Please see picture 4.3.
● Consider whether the installa�on environment is helpful to see the inverter LCD display and
indicator status clearly.
● Must offer a ven�late environment if inverter installed in the air�ght house.
Safety Hint:
Do not place or store any items next to the inverter.
Pic 4.2 Installa�on Angle
≤ °15
- 09 -
Pic 4.4 Inverter Installa�on
4.2 Inverter Installa�on
The inverter is designed according to the wall mounted type installa�on, please use the wall
mounted (the brick wall of the expansion bolt) when installing.
Pic 4.3 Installa�on Gap
Anchoring
Moun�ng bracket
Stainless steel screws
Inverter
500mm
500mm
- 10 -
2. Ensure that the posi�on of the installa�on holes on the wall is in accordance with the
moun�ng plate, and the moun�ng rack is horizontally placed.
3. Hang the inverter to the top of the moun�ng rack and then use the M4 screw in the
accessory to lock inverter heat sink to the hanging plate, to ensure that the inverter will not
move.
Procedure shows below:
1. Locate on the appropriate wall according to the bolt posi�on on the moun�ng bracket, then
mark the hole.On the brick wall, the installa�on must be suitable for the expansion bolt
installa�on.
Pic 4.5 Inverter hanging plate installa�on
Pic 4.6 Inverter installa�on
- 11 -
5.1 DC input terminal connec�on
5 Electrical Connec�on
Table 5.1 DC Cable Specifica�ons
1. Switch the Grid Supply Main Switch(AC)OFF.
2. Switch the DC lsolator OFF.
3. Assemble PV input connector to the inverter.
Safety Hint:
Please don’t connect PV array posi�ve or nega�ve pole to the ground, it could
cause serious damages to the inverter.
Safety Hint:
Before connec�ng inverter, please make sure the PV array open circuit voltage is
within the 1000V of the inverter.
Safety Hint:
Before connec�on, please make sure the polarity of the output voltage of PV
array matches the “DC+” and “DC-” symbols.
Safety Hint:
Please use approved DC cable for PV system.
Cable type Range Recommended value
Cross seconmm )
Industry generic PV cable
(model: PV1-F)
4.0~6.0
(12~10AWG) 4.0(12AWG)
Pic 5.1 DC+ male connector (MC4) Pic 5.2 DC- female connector (MC4)
- 12 -
The steps to assemble the DC connectors are listed as follows:
a)Strip off the DC wire about 7mm, disassemble the connector cap nut (see picture 5.3).
b) Crimping metal terminals with crimping pliers as shown in picture 5.4.
c) Insert the contact pin to the top part of the connector and screw up the cap nut to the top
part of the connector. (as shown in picture 5.5).
Pic 5.3 Disassemble the connector cap nut
7mm
7mm
Pic 5.5 connector with cap nut screwed on
Pic 5.4 Crimp the contact pin to the wire
- 13 -
5.2 AC input terminal connec�on
,shown as
picture 5.6

AC side of the inverter, the AC side is equipped with Three phase AC terminals that can be
-


Warning:
Sunlight shines on the panel will generate voltage, high voltage in series may

panel needs to be blocked by the opaque material and the DC switch should
be 'OFF', otherwise, the high voltage of the inverter may lead to life-


Warning:


Warning:
Use the DC power connector of the accessories. Do not interconnect the

Outside cable

Cable CSAModel Cable outer dia BreakerAWG Max cable length

15KW-LV 810mm 15-18mm 
- 14 -
The AC output connector is divided into three parts: matching socket, sleeve and sealing-
sleeve, as shown in picture 5.7, the steps are as follows:
Step 1: Remove the cable sealing ring and sleeve in sequence from the AC connector.
Step 2: Use strippers to strip the protec�ve sheath and insula�on layer of the AC cable to the
right length, as shown in Picture 5.8.
Step 3: Insert the cable (L1, L2, L3, N PE) into the sealing sleeve.
Step 4: Use the hexagon screwdriver, loosen the bolts of the socket in turn, and insert each
cable core into the corresponding jack, and set each screw. The connec�on hole of AC
connec�on terminal labeling is shown in Picture 5.9.
Warning:
Be careful to dis�nguish the L1, L2,L3,N and PE of the AC cables.
1. Matching socket 2.Sleeve 3.Sealing core 4.Sealing nut
Pic 5.7 AC connector structure
Pic 5.8 Strip AC cable
8~15mm
40mm
1234
- 15 -




- 16 -
5.3 The connec�on of the ground line
Good grounding is good for resis�ng surge voltage shock and improving EMI perfor-
mance.Therefore, before connec�ng AC, DC and communica�on cables, you need to ground
the cable firstly. For a single system, just ground the PE cable. For mul�ple machine systems,
all PE cables of the inverter need to be connected to the same grounding copper platoon to
ensure the equipoten�al connec�on. The installa�on of the shell ground wire is shown as
picture 5.11.
Warning:
Inverter has built-in leakage current detec�on circuit, If an external leakage
current protec�on device is connected, its opera�ng current must be greater
than 300 mA or higher, otherwise inverter may not work properly.
Pic 5.11The installa�on of the shell ground wire
- 17 -
5.4 Max. over current protec�on device
In order to protect the inverter AC connec�on, it is recommended to install a circuit breaker to
prevent overcurrent. See table 5.3 below.
Table 5.3 Recommended current protector specifica�ons
5.5 Inverter monitoring connec�on
Inverter has the func�on of wireless remote monitoring. The inverter with Wi-Fi func�on is
equipped with Wi-Fi Plug to connect the inverter and network. Wi-Fi Plug's opera�on,
installa�on, Internet access, APP downloading and other processes are detailed in the
instruc�ons.
PC
Router
WIFI
GPRS
Web Server
Phone
Pic 5.12 Internet monitoring solu�on
Rated output
voltage(V)
Inverter Rated output
current(A)
Current for protecon
device(A)
SUN-10K-G03-LV 127 3526.2
SUN-12K-G02-LV 127 4031.5
SUN-15K-G02-LV 127 5039.4
- 18 -

5.7 Configura�on of datalogger
6. Startup and Shutdown



that the two inputs be connected to the same number of photovoltaic modules.






sealed plate as shown in Picture 5.14. When installing the datalogger, remove the sealing plate,



power on. When the inverter is on the DC power, it is determined whether the datalogger is

5.6 Installa�on of datalogger

- 19 -
WARNING:
NOTE:
6.1 Start up the inverter
6.2 Inverter Shutdown
6.3 An�-PID Func�on(op�on)
When start up the three phase string inverter, should fellow below steps
1. First switch on the AC breaker.


3. When the ac voltage and DC voltage are normal, the inverter start-up is readyto begin.

crystal will show that the inverter is self-checking.
4. If the parameter is within acceptable range, the inverter will generate energy.
NORMAL indicator light is on.



connector. The inverter will close the LCD and all LED within two minutes.

runs when connected to AC.

PE
V-
V
T
S
R
Inverter
PID
PV-
PV
...

will create 450VDC between the PV and ground.No control and equipment are required.


- 20 -

current power to control the output power of the inverter, so that the power of inverter and





are the interface between three sets of current sensor and one set of control terminals. SUN limiter
will collect voltage and current from these interfaces and send control signals to the inverter.
L1 L1(L)L1(K)L2(L)L2(K)L3(L) L3(K) + -L2 L3 N
7 Zero export func�on via SUN limiter
7.1 SUN Limiter func�on wiring diagram
Pic 7.1 SUN Limiter view

requirements of chapter 5, if you has been running your inverter , and you want to use the limiter




- 21 -
U
V
L1(L)
Solar panels
Distribution Box
Limiter
Control signal
L1(K)
L2(L)
L2(K)
L3(L)
L3(K)
L1
L2
L3
N
W
N
Control signal

of the AC switchis determined by the load capacity.The AC switch we recommend to connect to
the inverter output refer to Table 5.2.
7.2 Connect the SUN limiter to inverter
The SUN limiter will measure the voltage and current of three phases separately, and this manual


Pic 7.2 Wiring diagram






Only when the SUN limiter collects the voltage and current of the same phase can it judge the
power of the phase. So the clamp senor should be connected to the same phase as the before.
Open the side buckle of the clamp senor, then clamp the senor to the AC line on the DC switch,




ACDC AlarmNormal
ACDC AlarmNormal
- 22 -
Pic 7.5 Waterproof terminal Pic 7.6 Connect limiter to inverter
1 2
limiter
+ -
1
2



the same on the waterproof terminal of the inverter. Twist the waterproof terminal and connect

the terminal to the interface of the SUN limiter. The other side of the line should be connected to
the control terminal.
Pic 7.3 Clamp Senor Pic 7.4 Clamp Senor internal arrow
L
K
Load
- 23 -
Pic 7.9 Limit switch







be completed. Shown as picture 7.10.


1. Turn on the AC switch





7.3 Use of zero export func�on
Pic 7.7 Connect terminal to inverter
System Param
Param
<<
0FF <<Limiter
Run
Meter OFF
- 24 -
7.4 Zero-export func�on (Op�on)
7.4.1 Zero-export func�on via energy meter




to connect the energy meter.

-

switch are determined by the power of load.
If there is no integrated DC switch inside the inverter you purchased, we commend you to
connect the DC switch. The voltage and current of the switch depend on the PV array you
access.
Utility Power:
20W

ON <<Limiter



chapter 7.9.









Meter OFF
* This item is not avaiable for some FW verison
- 25 -
Pic 7.11 Eastron meterEastron SDM630-Modbus V2
Grid
RS 485
RS 485 B RS 485 A
B A G
(5,6,7,8)
(1,2,3,4)
Pic 7.12 Connec�on diagram of Eastron meter
Solar Panel array Inverter
meter
AC Breaker
Grid
RS485 Communication
Family load
L1 L2 L3 N
L1 L2 L3 N
L1 L2 L3 N
L1 L2 L3 N
N L3 L2 L1
VCC_5V 485_B
485_B
485_A
485_A
GND
GND
RS 485
Male
connector
RS 485
Female connector
1
2
3
4
1 2 3 4 5 6 7 8
GND
Eastron
5 6 7 8
5 6 7 8
- 27 -
Pic 7.14 CHINT meter
Three-Phase Smart Meter
SET ESC
1 74 10
2524
3 96 10
RS 485
CHINT DTSU666
(3,6,9,10)
(1,4,7,10)
Pic 7.14 Connec�on diagram of CHINT meter
Solar Panel array
Inverter
meter
AC Breaker
Grid
RS485 Communication
Family load
1 74 10
2524
3 96 10
Three-Phase Smart Meter
SET ESC
L1 L2 L3 N
L1 L2 L3 N
N L3 L2 L1
VCC_5V 485_B
485_B
485_A
485_A
GND
RS 485
Male connector
RS 485
Female connector
1
2
3
4
- 28 -
7.4.2 Use of zero-export func�on
Pic 7.14 Meter switch
System Param
Param
<<
Island OFF
0FF <<Meter
Run

1. Turn on the AC switch.





picture 7.14.
Meter Power:
20W















- 29 -
Safety Hint:



(when using SUN limiter, the arrow of current sensor points to the load)
High Temperature Hazard:


cannot able to normal operate.



Warning:


inverter more responsive to limit the power.


grid(
feed into grid)
But please
don’t setup “Meter ON”. Also, you will be able to browse the load power on the monitoring




- 30 -
And then choose your system type as “Self-consump�on”
Secondly, go to plant page, if it shows the PV power, load power and grid power, which means
the configura�on is correct.
-31 -



Up key and the Down key to see the current DC voltage, DC current, AC voltage, AC current,in-

inverter.



Start

Setup
*PV VA
System param
Running param

Comm. param

Device

Fault record
LCD Main menu
Total DC Power
PV1 and Power
UA and UB
UC and Freq
*Meter
Time
E-Day and E-Total
*ImpEp and Total
*Load
*LoadEp and Total

successfully. Otherwise, it won't show.
- 32 -
Pic 8.2 The ini�al interface
Power: 0W
State: Standby
Power: 0W
State: Com.Error
Press UP or Down, you can check inverter DC voltage, DC current, AC voltage, AC current and
inverter temperature.
Pic 8.3 PV input voltage and current
informa�on
Total DC POWER:
0W
Pic 8.5 Grid voltage and current informa�on
UA: 234V 0.0A
UB: 0V 0.0A
Pic 8.6 Grid voltage and frequency
UC: 0V 0.0A
Freq: 0.00Hz
Pic 8.7 Time
21 - 05 - 2020
15 : 57 : 08
Pic 8.8 Meter power
Meter
Power: 0W
ImpEp: Daily energy purchased from grid;
Total: Total energy purchased from grid.
Pic 8.9 Electrical energy
ImpEp: 0.00KWh
Total : 0.00KWh
ExpEp: Daily energy sold to grid;
Total: Total energy sold to grid.
Pic 8.10 Electrical energy
ExpEp: 0.00KWh
Total : 0.00KWh
Pic 8.4 Load power
Power: 0W
PV1: 0.0V 0.0A
- 33 -

on the error code.
Pic 8.14 Fault Record
8.2.2 Fault Record
Device Info.
Fault Record <<
1 F35 220125 08
2 F56 220124 20






LoadEp: 0.00KWh
Total : 0.00KWh
E-Day : 0Wh
E-Total : 134KWh



8.2.1 Device informa�on
Device Info. <<
Fault Record
GL3000 SN-01
ID:2222224332
ID:2222224332
Inv1400
Inv1400
Lcd0235

8.2 Submenus in the Main Menu