Thermistor Probe Kit
DDSX / DDFM Thermistor Probe Installation
SAFETY SECTION
WARNING – Risk of Fire or Electrical Shock
Disconnect the power at the circuit breaker(s) or disconnect the switch(es)
before installing or servicing.
More than one circuit breaker or disconnect switch may be required to
de-energize the equipment before servicing.
Installation and/or wiring must be in accordance with the national and local
electrical code requirements.
Use #18-14 AWG - COPPER conductors ONLY.
Keep the enclosure door closed at all times when not servicing, if applicable.
Replace the dead front after service or installation, if applicable.
Only use the Intermatic® Thermistor Probe Kit supplied for the DDSX or DDT40
models. The probe connection(s) to the DDSX control are NOT an isolated Class
2 circuit.
AVERTISSEMENT – Risque d’incendie ou de choc électrique
Utiliser des fils n° 18 à 14 AWG - Conducteurs en CUIVRE UNIQUEMENT.
NOTICE
Rotate the timer dial clockwise only, rotating counter-clockwise will damage the
timer within installed control.
Do not move the clock hands on the timer within installed control. Moving the
clock hands manually may damage the timer.
The thermistor wire may be extended up to 400 ft (122 m) using field-supplied
wiring between the DDSX control and the thermistor probe location.
This product is only intended to be used with the DDSX and DDT40 model series.
All trademarks are the property of their respective owners.
PRODUCT DESCRIPTION
The thermistor probe kit allows you to add additional probes to your existing adaptive defrost control. Up to four thermistor
probes may be added to monitor multiple evaporator coils. To order additional thermistor probe kits (for example, to connect
multiple evaporators to one control), use part number 178GR10K-1.
Thermistor Probe Contents Part Number 178GR10K-1
The kit includes:
One thermistor probe, with clip
One input lead
Four wire connectors
FIG. 1. Thermistor Probe Kit Contents
2
Thermistor Probe Kit
Specications
Environmental Ratings:
Operating temperature: -40° F to 130° F
(-40° C to 55° C)
Operating humidity: 0-95 RH % non-condensing
Thermistor Probe Ratings:
NTC thermistor with a resistance of 10 K Ω
Construction includes:
Protective copper sheath for good thermal
conductivity
Removable stainless steel retaining clip
#24 AWG wire leads with PVC insulation
Thermistor probe wire length: 10 ft (3.05 m)
Input lead length: 6 ft (1.83 m)
INSTALLATION
Tools Required
Needle nose pliers
Wire cutter
Wire stripper
Pre-Installation
1. Disconnect all power to the unit at the circuit breaker or
disconnect switch. You may need to disconnect more
than one circuit breaker or switch.
2. Plan the length of field-supplied copper wire needed
to connect the thermistor probe from the evaporator
coil to the input lead. (This wire may be up to 400 ft
(121.92m) long)
Note: The field-supplied wires may run along with the
power wires through existing or new conduit.
3. If present, open the enclosure door.
4. If present, remove the existing dead front cover. See
FIG. 2.
FIG. 2. Existing Dead Front
Install the Thermistor Probe
Note: Refer to WARNINGS on page 1 before
proceeding.
1. Connect the input lead to the CUBE™ module as I
shown in FIG. 3. The input lead may be inserted into
any of the four connectors on the CUBE™ module.I
FIG. 3. Attach the Input Lead
3
Thermistor Probe Kit
2. Route the input lead above and around the CUBE™ I
module as shown in FIG. 4.
3. Route the length of field-supplied copper wire needed
to connect the thermistor probe from the evaporator
coil to the input lead. (This wire may be up to 400 ft
(121.92m) long)
Note: The field-supplied wires may run along with the
power wires through existing or new conduit.
4. Cut the input lead to the appropriate length:
For enclosure installations, cut the input lead so the
connection will fit inside the enclosure, as shown in
FIG. 6.
For bracket installations, cut the input lead to an
appropriate length inside the condensing unit control
panel.
5. Use the provided wire connectors to connect the input
lead to the routed field-supplied wire. FIG. 4. Route Input Lead (Shown with 2 Probes Routed)
6. Connect the thermistor probe to the evaporator coil.
There are two options for optimal probe placement.
Insert the probe between the cooling fins, as shown
in FIG. 5. Ensure that the probe makes good contact
with one of the evaporator tubes. Then, using needle
nose pliers, carefully bend the cooling fins together
to hold the probe firmly in place.
Use the provided clip, as shown in FIG. 6. Clip the
probe onto one of the lower coils in either the
10 o’clock or 2 o’clock position, making sure that
the probe makes good contact with the evaporator
tube.
Note: Position the probe wherever frost accumulates
most quickly. This is generally 1 to 2 (2.5 cm to " "
5 cm) from either end and at the bottom quarter
of the evaporator coil. If there is uncertainty about
where frost typically accumulates the fastest, put
the system into a manual defrost (see “Optional:
Manual Defrost” on page 5) and monitor the
last area of the evaporator where frost is present
prior to a completely frost-free coil.
Make sure the sensor probe is not fastened in close
proximity to the defrost heating element.
7. Route the thermistor probe wires away from the
evaporator fans and cooling fins, avoiding pinches and
strain. You can route the wire through existing or new
line voltage conduits. Secure the wires as appropriate
for your installation.
8. Use the provided wire connectors to connect the
thermistor probe wire to your length of field-supplied
copper wire.
9. Use electrical tape to protect all connections against
moisture.
FIG. 5. Insert Thermistor Probe between Evaporator Cooling Fins
FIG. 6. Connect Thermistor Probe to Evaporator Coil