PCE Instruments PCE-IT55 Käyttöohje
PCE Instruments
Mittauslaitteet
PCE-IT55
Lue alta 📖 käyttöohje suomeksi merkille PCE Instruments PCE-IT55 (7 sivua) kategoriassa Mittauslaitteet. Tämä opas oli hyödyllinen 2 henkilölle ja sai 4.5 tähden keskimäärin 2 käyttäjältä
Sivu 1/7
1 2
DIGITAL INSULATION TESTER
INSTRUCTION MANUAL
SAFETY INFORMATION
Read the following safety information carefully before
attempting to operate or service the meter.
To avoid damages to the instrument do not apply the
signals which exceed the maximum limits shown in the
technical specifications tables.
Do not use the meter or test leads if they look damaged.
Use extreme caution when working around bare
conductors or bus bars.
Accidental contact with the conductor could result in
electric shock.
Use the meter only as specified in this manual;
otherwise, the protection provided by the meter may be
impaired.
Read the operating instructions before use and follow
all safety Information.
Caution when working with voltages above 60V DC or
30V AC RMS. Such voltages pose a shock hazard.
Before taking resistance measurements or testing
acoustic continuity, disconnect circuit from main power
supply and all loads from the circuit.
3 4
Safety symbols:
Caution refer to this manual before using the meter.
Dangerous voltages.
Meter is protected throughout by double insulation or
reinforced insulation.
When servicing, use only specified replacement parts.
CE Comply with EN-61010-1
1. SPECIFICATIONS
1-1 General Information
Environment conditions:
①①①① Installation Categories II
②②②② Pollution Degree 2
③③③③ Altitude up to 2000 meters
④
④④
④
Indoor use only
⑤⑤⑤⑤ Relatively humidity 80% max.
⑥
⑥⑥
⑥
Operation Ambient 0~40ºC
Maintenance & Clearing:
①
①①
①
Repairs or servicing not covered in this manual should
only be performed by qualified personnel.
②②②② Periodically wipe the case with a dry cloth. Do not use
abrasives or solvents on this instruments.
Display: Large LCD with dual display
Measurement Range: 200 , 200k , 200M /250V, Ω Ω Ω
200M /500V, 2000M /1000V, Ω Ω
750V/ACV, 1000V/DCV.
Sampling Rate: 2.5 times per second.
Zero Adjustment: Automatic adjustment.
Over Range Indicator: Number 1 of highest digit is
displayed.
Low Battery Indication: The is displayed when the
battery Voltage drop below the
operating voltage.
Operating Temperature: 0ºC to 40ºC (32ºF to 104ºF) and
Humidity below 80% RH
Storage Temperature: -10ºC to 60ºC (14ºF to 140ºF) and
Humidity below 70% RH
Power source: DC9V (6x1.5V Size “AA” battery or Equivalent)
Dimensions: 200(L) x 92(W) x 50(H) mm
Weight: Approx 700g include battery
Accessories: Test leads, 6pcs battery, Carrying case, manual.
5 6
1-2 Electrical Specifications
Accuracies are specified in the way:
±(…% of reading +…digits) at 23ºC 5ºC,below 80% RH. ±
OHMS
Range Resolution
Accuracy
Max. open
Circuit
Voltage
Overload
Protection
200 0.1 Ω Ω
+(1%+2) 4.5V 250Vrms
200k 0.1k 3.0V Ω Ω
Continuity Beeper
Range Resolution
Operation
Resistance
Max.open
Circuit
Voltage
Overload
Protection
•))) 0.1
Ω
Resistance 40≤
Ω
4.5V 250Vrms
Short circuit current 200mA ≤
DC Voltage
Range Resolution Accuracy Input
Impedance
Overload
Protection
1000V 1V +(0.8%+3) 10M 1000Vrms Ω
AC Voltage (40Hz~400Hz)
Range Resolution
Accuracy Input
Impedance
Overload
Protection
750V 1V +(1.2%+10)
10M 750Vrms Ω
Meg OHMS
Range Resolution Accuracy Terminal Voltage
200M
Ω
/250V 0.1M
Ω
+(3%+5)
250V+10%~-0%
200M
Ω
/500V 0.1M
Ω
500V+10%~-0%
0~1000M
Ω
/1000V
1M
Ω
1000V+10%~-0%
1000~2000M
Ω
/1000V
+(5%+5)
Range Test Current Short circuit current
200M /250V Ω
1mA
250K (load) Ω
≤
1mA
200M /500V 500K (load) Ω Ω
0~1000MΩ
/1000V 1M Ω
1000~2000MΩ
/1000V
Tuotetiedot
Merkki: | PCE Instruments |
Kategoria: | Mittauslaitteet |
Malli: | PCE-IT55 |
Tarvitsetko apua?
Jos tarvitset apua merkille PCE Instruments PCE-IT55 esitä kysymys alla ja muut käyttäjät vastaavat sinulle
Mittauslaitteet PCE Instruments Käyttöohjeet
24 Lokakuuta 2024
23 Lokakuuta 2024
23 Lokakuuta 2024
23 Lokakuuta 2024
23 Lokakuuta 2024
23 Lokakuuta 2024
23 Lokakuuta 2024
23 Lokakuuta 2024
23 Lokakuuta 2024
23 Lokakuuta 2024
Mittauslaitteet Käyttöohjeet
- Mittauslaitteet Kogan
- Mittauslaitteet PeakTech
- Mittauslaitteet Clean Air Optima
- Mittauslaitteet CSL
- Mittauslaitteet Kern
- Mittauslaitteet Einhell
- Mittauslaitteet Reely
- Mittauslaitteet Joy-it
- Mittauslaitteet Basetech
- Mittauslaitteet Gossen Metrawatt
- Mittauslaitteet TFA
- Mittauslaitteet Extech
- Mittauslaitteet Sonel
- Mittauslaitteet Flir
- Mittauslaitteet Testo
Viimeisimmät Mittauslaitteet Käyttöohjeet
27 Lokakuuta 2024
26 Lokakuuta 2024
25 Lokakuuta 2024
25 Lokakuuta 2024
24 Lokakuuta 2024
22 Lokakuuta 2024
22 Lokakuuta 2024
21 Lokakuuta 2024
21 Lokakuuta 2024
21 Lokakuuta 2024